B089: Monitor display select for networked inverter – When the L200

2

inverter is

controlled via network, the inverter’s keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 will be displayed on the keypad. See

“Local Monitoring During Network Operation” on page 3–8

for more details.

B130/B131:

Over-voltage LADSTOP Enable / Over-voltage LADSTOP Level –

The over-

voltage LADSTOP function monitors the DC bus voltage and actively changes the
output frequency profile to maintain the DC bus voltage within settable limits. Although
“LAD” refers to “linear acceleration / deceleration,” the inverter only “STOPs” the
deceleration slope so that regenerative voltage will not cause the DC bus to rise enough
to cause an over-voltage trip event. Note that acceleration is not affected.

B089 Monitor display select

for networked inverter

Selects the parameter
displayed on the keypad
display when the inverter is
networked, 7 options:
01... Output frequency monitor
02... Output current monitor
03... Rotation direction
monitor
04... Process variable (PV),
PID feedback monitor
05... Intelligent input terminal
status
06... Intelligent output terminal
status
07... Scaled output frequency
monitor

✔ ✔

01

01

PANEL d001

B091 Stop mode selection

Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)

✘ ✘

00

00

STP Slct DEC