Network Protocol Reference

Appendix B

B–6

Network Protocol Reference

Transmission procedure

The transmission between the external control equipment and the inverter takes the
procedure below

• Query - A frame sent from the external control equipment to the inverter

• Response - A frame returned from inverter to the external control equipment

The inverter returns the response only after the inverter receives a query from the
external control equipment and does not output the response positively. Each frame is
formatted (with commands) as follows:

Message Configuration: Query

Slave address:

• This is a number of 1 to 32 assigned to each inverter (slave). (Only the inverter having

the address given as a slave address in the query can receive the query.)

• When slave address “0” is specified, the query can be addressed to all inverters simul-

taneously. (Broadcasting)

• In broadcasting, you cannot call and loop back data.

Frame Format

Header (silent interval)

Slave address

Function code

Data

Error check

trailer (silent interval)

Query

t

External control

equipment

Response

Inverter

Latency time

(silent interval plus C078 setting)