When writing in a selected coil fails, see the exception response.

Write in Holding Register [06h]:

This function writes data in a specified holding register. An example follows:

• Write “50Hz” as the first Multi-speed 0 (A020) in an inverter having slave address

“5.”

• This example uses change data “500(1F4h)” to set “50Hz” as the data resolution of the

register “003Ah” holding the first Multi-speed 0 (A020) is 0.1Hz

When writing in a selected holding register fails, see the exception response.

Query:

Note 1:

No response is made for a
broadcasting query.

Response:

No.

Field Name

Example

(Hex)

1

Slave address *1

05

2

Function code

06

3

Register start number
(high order)

00

4

Register start number
(low order)

3A

5

Change data
(high order)

01

6

Change data
(low order)

F4

7

CRC-16 (high order)

A8

8

CRC-16 (low order)

54

No.

Field Name

Example

(Hex)

1

Slave address

05

2

Function code

06

3

Register start
number (high order)

00

4

Register start
number (low order)

3A

5

Change data
(high order)

01

6

Change data
(low order)

F4

7

CRC-16 (high order)

A8

8

CRC-16 (low order)

54