Connecting the inverter to modbus, Connecting the inverter to modbus b–3, Setting. see – Hitachi L2002 User Manual

Page 239: Appendix b

Advertising
background image

L200

2

Inverter

Appendix B

B–3

Connecting the Inverter to ModBus

Follow the steps in this section to connect the inverter to the ModBus network.

1. Open Serial Port Cover - The inverter keypad has a hinged dust cover protecting the

serial port connector. Lift the cover from the bottom edge, and tilt upward as shown
(below left).

2. Modular Interconnect Removal - With the serial port cover opened, notice the RJ45

modular connector behind it. Connect the serial cable and engage the locking tab in
the connector as shown (below right).

3. Cable Wiring - The inverter communications

port uses RS485 differential transceiver. The
pinout is shown to the right and listed below. Be
sure the cable connection you make matches the
diagram.

Pin

Symbol

Description

1

Not used. Do not connect

2

Not used. Do not connect

3

Not used. Do not connect

4

Not used. Do not connect

5

SP

Send/Receive data Positive

6

SN

Send/Receive data Negative

7

Not used. Do not connect

8

Not used. Do not connect

RJ45 modular

communications

connector

Dust

cover

Serial cable with RJ45 end

L200

2

1

2

RUN

STOP

RESET

FUNC.

STR

HITACHI

POWER

ALARM

RUN

A

Hz

PRG

5 0.0

S
N

1

S
P

2

3

4

5

6

7

8

Not used

Not used