• When a read coil is outside the defined coils, the final coil data to be transmitted

contains “0“as the status of the coil outside the range.

• When the Read Coil Status command cannot be executed normally, see the exception

response.

Read Holding Register [03h]:

This function reads the contents of the specified number of consecutive holding registers
(of specified register addresses). An example follows below.

• Reading previous three trip factors from an inverter having a slave address “5”

• This example assumes the previous three trip factors are as follows:

L200

2

Command

D081 (N)

D082 (N-1)

D083 (N-2)

Coil Number

0019h

001Ah

0018h

Trip factor

Over-voltage (E07)

Under-voltage (E09)

No trip

Query:

Note 1:

Broadcasting is disabled.

.Response:

Note 2:

Data is transferred by the
specified number of data bytes
(data size). In this case, 6 bytes
are used to return the content
of three holding registers.

No.

Field Name

Example

(Hex)

1

Slave address *1

05

2

Function code

03

3

Register start number
(high order)

00

4

Register start number
(low order)

19

5

Number of holding
registers (high order)

00

6

Number of holding
registers (low order)

03

7

CRC-16 (high order)

D5

8

CRC-16 (low order)

88

No.

Field Name

Example

(Hex)

1

Slave address

05

2

Function code

03

3

Data size (in bytes) *2

06

4

Register start number
(high order)

00

5

Register start number
(low order)

07

6

Register start number + 1
(high order)

00

7

Register start number +1
(low order)

09

8

Register start number + 2
(high order)

00

9

Register start number +2
(low order)

FF

10

CRC-16 (high order)

36

11

CRC-16 (low order)

37