“B” Group: Fine Tuning Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–42

B091/B088: Stop Mode / Restart Mode Configuration – You can configure how the
inverter performs a standard stop (each time Run FWD and REV signals turn OFF).
Setting B091 determines whether the inverter will control the deceleration, or whether it
will perform a free-run stop (coast to a stop). When using the free-run stop selection, it is
imperative to also configure how you want the inverter to resume control of motor speed.
Setting B088 determines whether the inverter will ensure the motor always resumes at
0 Hz, or whether the motor resumes from its current coasting speed (also called
frequency matching). The Run command may turn OFF briefly, allowing the motor to
coast to a slower speed from which normal operation can resume.

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

B080 [AM] analog signal

gain

Adjust of analog output at
terminal [AM],
range is 0 to 255

✔ ✔

100.

100.

AM-Adj 00100%

B082 Start frequency adjust-

ment

Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz

✘ ✔

0.5

0.5

Hz

fmin 0000.5Hz

B083 Carrier frequency

setting

Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz

✘ ✘

5.0

5.0

kHz

Carrier 0005.0

B084 Initialization mode

(parameters or trip
history)

Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization

✘ ✘

00

00

INIT Mode TRP

B085 Country code for initial-

ization

Select default parameter values
for country on initialization,
four options, option codes:
00... Japan version
01... Europe version
02... US version

✘ ✘

01

02

INIT Slct USA

B086 Frequency scaling

conversion factor

Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9

✔ ✔

1.0

1.0

Cnv Gain 0001.0

B087 STOP key enable

Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled

✘ ✔

00

00

STP Key ON