Electronic thermal overload alarm setting – Hitachi L2002 User Manual

Page 115

Advertising
background image

L200

2

Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–35

Electronic Thermal Overload Alarm Setting

The thermal overload detection protects the
inverter and motor from overheating due to
an excessive load. It uses a current/inverse
time curve to determine the trip point.

First, use B013 to select the torque charac-
teristic that matches your load. This allows
the inverter to utilize the best thermal
overload characteristic for your application.

The torque developed in a motor is directly
proportional to the current in the windings,
which is also proportional to the heat generated (and temperature, over time). Therefore,
you must set the thermal overload threshold in terms of current (amperes) for parameter
B012. The range is 20% to 120% of the rated current for each inverter model. If the
current exceeds the level you specify, the inverter will trip and log an event (error E05) in
the history table. The inverter turns the motor output OFF when tripped. Separate
settings are available for the second motor (if applicable) as shown in the following
table.

Output frequency

Constant torque

Reduced

torque

B013 = 01

B013 = 00

Torque

5

20

60

120

Hz

100%

80%

60%

0

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

B012 Level of electronic

thermal setting

Set a level between 20% and
120% for the rated inverter
current.

✘ ✔

Rated current

for each inverter

model *1

A

E-THM LVL001.60A

B212 Level of electronic

thermal setting, 2nd
motor

Set a level between 20% and
120% for the rated inverter
current.

✘ ✔

Rated current

for each inverter

model *1

A

2ETHM LVL 01.60A

B013 Electronic thermal

characteristic

Select from two curves, option
codes:
00 .. Reduced torque 1
01 .. Constant torque
02 .. Reduced torque 2

✘ ✔

01

01

E-THM CHAR CRT

B213 Electronic thermal

characteristic, 2nd
motor

Select from two curves, option
codes:
00 .. Reduced torque 1
01 .. Constant torque
02 .. Reduced torque 2

✘ ✔

01

01

2ETHM CHAR CRT