Hitachi L2002 User Manual

Page 99

Advertising
background image

L200

2

Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–19

Be aware that running the motor at a low speed for a long time can cause motor
overheating. This is particularly true when manual torque boost is ON, or if the motor
relies on a built-in fan for cooling.

NOTE: Manual torque boost applies only to constant torque (A044=00) and variable
torque (A044=01) V/f control.

Voltage Gain – Using parameter A045 you
can modify the voltage gain of the inverter (see
graph at right). This is specified as a percent-
age of the full scale output voltage. The gain
can be set from 20% to 100%. It should be
adjusted in accordance with the motor specifi-
cations.

The following table shows the methods of
torque control selection.

V

100%

20%

Hz

Voltage Gain

0

A045

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

A041 Torque boost select

Two options:
00 .. Manual torque boost
01 .. Automatic torque boost

✘ ✘

00

00

%

V-Bst Slct MN

A241 Torque boost select, 2nd

motor

Two options:
00 .. Manual torque boost
01 .. Automatic torque boost

✘ ✘

00

00

%

2VBst Slct MN

A042 Manual torque boost

value

Can boost starting torque
between 0 and 20% above
normal V/f curve,
range is 0.0 to 20.0%

✔ ✔

1.8

1.8

%

V-Bst V 0005.0%

A242 Manual torque boost

value, 2nd motor

Can boost starting torque
between 0 and 20% above
normal V/f curve,
range is 0.0 to 20.0%

✔ ✔

0.0

0.0

%

2VBst V 0000.0%

A043 Manual torque boost

frequency adjustment

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque
boost, range is 0.0 to 50.0%

✔ ✔

10.0

10.0

%

M-Bst F 0003.0%

A243 Manual torque boost

frequency adjustment,
2nd motor

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque
boost, range is 0.0 to 50.0%

✔ ✔

0.0

0.0

%

2MBst F 0000.0%

A044 V/f characteristic curve

selection

Two available V/f curves;
three select codes:
00 .. Constant torque
01 .. Reduced torque

✘ ✘

00

00

CTRL C-TRQ

Advertising