B–36, Appendix b – Hitachi L2002 User Manual

Page 272

Advertising
background image

ModBus Data Listing

Appendix B

B–36

B083

Carrier frequency
setting

R/W Sets the PWM carrier (inter-

nal switching frequency),
range is 2.0 to 14.0 kHz

10D2h 04306

20 to

140

0.1 Hz

B084

Initialization mode
(parameters or trip
history)

R/W Select the type of initializa-

tion to occur, two option
codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization

10D3h 04307

0, 1, 2

B085

Country code for initial-
ization (not accessible
to ModBus)

Select default parameter
values for country on initial-
ization. Note: Write not
allowed from network.

10D4h 04308

B086

Frequency scaling
conversion factor

R/W Specify a constant to scale the

displayed frequency for D007
monitor, range is 0.1 to 99.9

10D5h 04309

1 to 999

0.1

B087

STOP key enable

R/W Select whether the STOP key

on the keypad is enabled, two
option codes:
00... enabled
01... disabled

10D6h 04310

0, 1

B088

Restart mode after FRS

R/W Selects how the inverter

resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)

10D7h 04311

0, 1

“B” Group Fine Tuning Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.