B–41, Appendix b – Hitachi L2002 User Manual

Page 277

Advertising
background image

L200

2

Inverter

Appendix B

B–41

C081

O input span calibration

R/W Scale factor between the

external frequency command
on terminals L – O (voltage
input) and the frequency
output, range is 0.0 to 200.0%

1141h

04417 0 to 2000

0.1 %

C082

OI input span calibra-
tion

R/W Scale factor between the

external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%

1142h

04418 0 to 2000

0.1 %

C085

Thermistor input tuning

R/W Range is 0.0 to 200.0%

1144h

04420 0 to 2000

0.1 %

C086

[AM] terminal offset
tuning

R/W Range is 0.0 to 10.0V

1145h

04421

0 to 100

0.1 V

C091

Debug mode enable

R

Displays debug parameters.
Two option codes:
00... Disable
01... Enable

1148h

04424

0, 1

C101

Up/Down memory
mode
selection

R/W Controls speed setpoint for

the inverter after power cycle.
Two option codes:
00... Clear last frequency
(return to default frequency
F001)
01... Keep last frequency
adjusted by UP/DWN

1149h

04425

0, 1

C102

Reset selection

R/W Determines response to Reset

input [RST].
Three option codes:
00... Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01... Cancel trip state at signal
OFF transition, stops inverter
if in Run Mode
02... Cancel trip state at input
signal ON transition, no effect
if in Run Mode

114Ah 04426

0, 1, 2

C141

Input A select for logic
output

R/W

See

“Output Logic and

Timing” on page 3–61

1150h

04432 0, 1, 2, 3,

4, 5, 6, 7,

8, 9

C142

Input B select for logic
output

R/W

1151h

04433

“C” Group Intelligent Terminal Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.