Overload Advance Notice Signal

When the output current exceeds a preset
value, the [OL] terminal signal turns ON.
The parameter C041 sets the overload
threshold. The overload detection circuit
operates during powered motor opera-
tion and during regenerative braking. The
output circuits use open-collector
transistors, and are active low.

[OL]

Signal

1
0

ON

t

ON

Current

threshold

regeneration

power running

threshold

C041

C041

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

03

OL

Overload Advance
Notice Signal

ON

when output current is more than the set thresh-
old for the overload signal

OFF

when output current is less than the set threshold
for the overload signal

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

C041

Notes:

The default value is 100%. To change the level
from the default, set C041 (overload level).

The accuracy of this function is the same as the
function of the output current monitor on the [FM]
terminal (see

“Analog Output Operation” on

page 4–55

).

The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.

RY

+

Example (requires output configuration—
see page

3–54

):

Inverter output
terminal circuit

OL

Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages

4–36

and

3–54

):

AL0

AL2

AL1

Inverter logic
circuit board

See I/O specs
on page

4–6

.

OL

Load

Power

supply

12 11

CM2