L200

2

Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–15

A016:

External Frequency Filter Time Constant – This filter smooths the analog input signal

for the inverter’s output frequency reference.

• A016 sets the filter range n=1 to 16. This is a simple moving average calculation,

where n (number of samples) is variable.

• A016 = 17 is a special value. It configures the inverter to use a moveable deadband

feature. Initially the inverter uses the average of the previous 16 samples. Then, the
deadband is employed for each subsequent average of 16 samples. The deadband
works by ignoring small fluctuations in each new average: less than +0.1Hz or –0.2Hz
change. When a 16-sample average exceeds this deadband, then the inverter applies
that average to the output frequency reference, and it also becomes the new deadband
comparison point for subsequent sample averages.

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

A005 [AT] selection

Four options, select codes:
00 .. Select between [O] and
[OI] at [AT]
01 .. [O] + [OI] ([AT] input is
ignored)
02 .. Select between [O] and
keypad potentiometer
03 .. Select between [OI] and
keypad potentiometer

✘ ✔

00

00

Hz

AT-Slct O/OI

A011 O–L input active range

start frequency

The output frequency corre-
sponding to the analog input
range starting point,
range is 0.0 to 400.0

✘ ✔

0.0

0.0

Hz

O-EXS 0000.0Hz

A012 O–L input active range

end frequency

The output frequency corre-
sponding to the analog input
range ending point,
range is 0.0 to 400.0

✘ ✔

0.0

0.0

Hz

O-EXE 0000.0Hz

A013 O–L input active range

start voltage

The starting point (offset) for
the active analog input range,
range is 0. to 100.

✘ ✔

0.

0.

%

O-EX%S 00000%

A014 O–L input active range

end voltage

The ending point (offset) for
the active analog input range,
range is 0. to 100.

✘ ✔

100.

100.

%

O-EX%E 00100%

A015 O–L input start

frequency enable

Two options; select codes:
00 .. Use offset (A011 value)
01 .. Use 0 Hz

✘ ✔

01

01

O-LVL 0Hz

A016 External frequency

filter time constant

One range plus one setting:
01 to 16... Moving average,
where n=1 to 16 (number of
samples for average)
17 .. Use 16-sample average,
plus deadband +0.1/–0.2Hz.

✘ ✔

2.

8.

Sam-

ples

F-SAMP 00008