“H” Group: Motor Constants Functions

The “H” Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values to
match the motor. Parameter H006 is factory-
set. If you want to reset the parameters to the
factory default settings, use the procedure in

“Restoring Factory Default Settings” on
page 6–8

. Use A044 to select the torque

control algorithm as shown in the diagram.

NOTE: If you are using automatic torque boost (A041/A241 = 01) and the output
current is unstable in the low frequency range, be sure to adjust A042/A242 and
A043/A243 with H006/H206 in order to decrease the boost voltage as an addition to the
standard V/f curve.

Output

A44

V/f control,

constant torque

V/f control,

variable torque

00

01

Inverter Torque Control Algorithms

“H” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

H003 Motor capacity

Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11

✘ ✘ Specified by the

capacity of each

inverter model

kW

AUX K 0.4 kW

H203 Motor capacity, 2nd

setting

Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11

✘ ✘

kW

2AUXK 0.4 kW

H004 Motor poles setting

Four selections:
2 / 4 / 6 / 8

✘ ✘

4

4

poles

AUX P 4p

H204 Motor poles setting, 2nd

motor

Four selections:
2 / 4 / 6 / 8

✘ ✘

4

4

poles

2AUXP 4p

H006 Motor stabilization

constant

Motor constant (factory set),
range is 0 to 255

✔ ✔

100

100

AUX KCD 100

H206 Motor stabilization

constant, 2nd motor

Motor constant (factory set),
range is 0 to 255

✔ ✔

100

100

2AUXKCD 100