Signal Ratings

Detailed ratings are in

“Control Logic Signal Specifications” on page 4–6

.

Other functions

AVR function, curved accel/decel profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency, carrier
frequency change (2 to 14 kHz) *10, frequency jump, gain and bias
setting, process jogging, electronic thermal level adjustment, retry
function, trip history monitor, 2nd setting selection, fan ON/OFF
selection

Protective function

Over-current, over-voltage, under-voltage, overload, extreme high/
low temperature, CPU error, memory error, ground fault detection at
startup, internal communication error, electronic thermal

Operat-
ing
Environ
ment

Temperature

Operating (ambient): -10 to 40

°C (*10) / Storage: -25 to 60°C (*11)

Humidity

20 to 90% humidity (non-condensing)

Vibration *12

5.9 m/s

2

(0.6G), 10 to 55 Hz

Location

Altitude 1,000 m or less, indoors (no corrosive gasses or dust)

Coating color

Blue (DIC 14 Version No. 436)

Options

Remote operator unit, copy unit, cables for the units, braking unit,
braking resistor, AC reactor, DC reactor, noise filter, DIN rail
mounting

Item

General Specifications

Signal / Contact

Ratings

Built-in power for inputs

24VDC, 30 mA maximum

Discrete logic inputs

27VDC maximum

Discrete logic outputs

50mA maximum ON state current, 27 VDC maximum OFF state voltage

Analog output

0 to 10VDC, 1 mA

Analog input, current

4 to 19.6 mA range, 20 mA nominal

Analog input, voltage

0 to 9.6 VDC range, 10VDC nominal, input impedance 10 k

Ω

+10V analog reference

10VDC nominal, 10 mA maximum

Alarm relay contacts

250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min.
30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.
5 VDC, 100mA min.