Hitachi L2002 User Manual

Page 128

Advertising
background image

“C” Group: Intelligent Terminal Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–48

The input logic convention is programmable for each of the five inputs. Most inputs
default to normally open (active high), but you can select normally closed (active low) in
order to invert the sense of the logic.

C004 Terminal [4] function

Select terminal [4] function,
29 options (see next section)

✘ ✘

03

[CF2]

13

[USP]

IN-TM 4 USP

C204 Terminal [4] function,

2nd motor

Select terminal [4] function,
29 options (see next section)

✘ ✘

03

[CF2]

13

[USP]

2IN-TM 4 USP

C005 Terminal [5] function

Select terminal [5] function,
30 options (see next section)

✘ ✘

18

[RS]

09

[2CH]

IN-TM 5 2CH

C205 Terminal [5] function,

2nd motor

Select terminal [5] function,
30 options (see next section)

✘ ✘

18

[RS]

09

[2CH]

2IN-TM 5 2CH

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

C011 Terminal [1] active state Select logic convention, two

option codes:
00... normally open [NO]
01... normally closed [NC]

✘ ✘

00

00

O/C-1 NO

C012 Terminal [2] active state Select logic convention, two

option codes:
00... normally open [NO]
01... normally closed [NC]

✘ ✘

00

00

O/C-2 NO

C013 Terminal [3] active state Select logic convention, two

option codes:
00... normally open [NO]
01... normally closed [NC]

✘ ✘

00

00

O/C-3 NO

C014 Terminal [4] active state Select logic convention, two

option codes:
00... normally open [NO]
01... normally closed [NC]

✘ ✘

00

01

O/C-4 NC

C015 Terminal [5] active state Select logic convention, two

option codes:
00... normally open [NO]
01... normally closed [NC]

✘ ✘

00

00

O/C-5 NO