Hitachi L2002 User Manual

Page 188

Advertising
background image

Using Intelligent Output Terminals

Oper

ations

and Monitor

ing

4–44

The alarm relay output can be configured in two main ways:

Trip/Power Loss Alarm – The alarm relay is configured as normally closed

(C036=1) by default, shown below (left). An external alarm circuit that detects broken
wiring also as an alarm connects to [AL0] and [AL1]. After powerup and short delay
(< 2 seconds), the relay energizes and the alarm circuit is OFF. Then, either an inverter
trip event or an inverter power loss will de-energize the relay and open the alarm
circuit.

Trip Alarm – Alternatively, you can configure the relay as normally open (C036=0),

shown below (right). An external alarm circuit that detects broken wiring also as an
alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only when an
inverter trip event occurs, opening the alarm circuit. However, in this configuration, an
inverter power loss does not open the alarm circuit.

Be sure to use the relay configuration that is appropriate for your system design. Note
that the external circuits shown assume that a closed circuit = no alarm condition (so that
a broken wire also causes an alarm). However, some systems may require a closed
circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2]
from the ones shown.

N.C. contacts (C036=01)

N.O. contact (C036=00)

During normal operation

When an alarm occurs
or when power is OFF

During normal operation

or when power is OFF

When an alarm occurs

AL0

AL2

AL1

Power

supply

Alarm

device

AL0

AL2

AL1

Power

supply

Alarm

device

AL0

AL2

AL1

Power

supply

Alarm

device

AL0

AL2

AL1

Power

supply

Alarm

device

Power

Run

Mode

AL0–

AL1

AL0–

AL2

ON

Normal

Closed

Open

ON

Trip

Open

Closed

OFF

Open

Closed

Power

Run

Mode

AL0–

AL1

AL0–

AL2

ON

Normal

Open

Closed

ON

Trip

Closed

Open

OFF

Open

Closed