Determining wire and fuse sizes, Determining – Hitachi L2002 User Manual

Page 63

Advertising
background image

L200

2

Inverter

In

v

e

rt

er Mounting

and Installation

2–17

Determining Wire and Fuse Sizes

The maximum motor currents in your application determines the recommended wire
size. The following table gives the wire size in AWG. The “Power Lines” column applies
to the inverter input power, output wires to the motor, the earth ground connection, and
any other component shown in the

“Basic System Description” on page 2–7

. The

“Signal Lines” column applies to any wire connecting to the two green 8-position
connectors just inside the front panel half-door.

Note 1:

Field wiring must be made by a UL-listed and CSA-certified closed-loop
terminal connector sized for the wire gauge involved. Connector must be
fixed by using the crimping tool specified by the connector manufacturer.

Note 2:

Be sure to consider the capacity of the circuit breaker to be used.

Note 3:

Be sure to use a larger wire gauge if power line length exceeds 66 ft. (20m).

Note 4:

Use 18 AWG / 0.75 mm

2

wire for the alarm signal wire ([AL0], [AL1], [AL2]

terminals).

Note 5:

The inverter’s input power wiring must include UL Listed, dual-element,
600V fuses, or UL Listed, inverse-time, 600V circuit breakers.

Motor Output

(kW/HP)

Inverter Model

Wiring

Applicable
equipment

kW

HP

Power Lines

Signal Lines

Fuse / Breaker

0.2 1/4

L200-002NFE(F)2/NFU2

AWG16 / 1.3 mm

2

18 to 28 AWG /

0.14 to 0.75 mm

2

shielded wire

(see Note 4)

10A

0.4

1/2

L200-004NFE(F)2/NFU2

0.55

3/4

L200-005NFE(F)2

0.75

1

L200-007NFE(F)2/NFU2

AWG14 / 2.1 mm

2

15A

1.1

1 1/2

L200-011NFE(F)2

1.5

2

L200-015NFE(F)2/NFU2

AWG12 / 3.3 mm

2

20A (single ph.)

15A (three ph.)

2.2

3

L200-022NFE(F)2/NFU2

AWG10 / 5.3 mm

2

30A (single ph.)

20A (three ph.)

3.7

5

L200-037LFU2

AWG10 / 5.3 mm

2

30A

5.5

7 1/2

L200-055LFU2

AWG10 / 5.3 mm

2

40A

7.5

10

L200-075LFU2

AWG8 / 8.4 mm

2

50A

0.4

1/2

L200-004HFE(F)2/HFU2

AWG16 / 1.3 mm

2

3A

0.75

1

L200-007HFE(F)2/HFU2

6A

1.5

2

L200-015HFE(F)2/HFU2

10A

2.2

3

L200-022HFE(F)2/HFU2

3.0

4

L200-030HFE(F)2

AWG14 / 2.1 mm

2

15A

4.0

5

L200-040HFE(F)2/HFU2

5.5

7 1/2

L200-055HFE(F)2/HFU2

AWG12 / 3.3 mm

2

20A

7.5

10

L200-075HFE(F)2/HFU2

25A

Advertising