Instantaneous power failure / under-voltage alarm – Hitachi L2002 User Manual

Page 114

Advertising
background image

“B” Group: Fine Tuning Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–34

Instantaneous Power Failure / Under-voltage Alarm

Use parameter B004 to disable or enable the instantaneous power failure / undervoltage
alarm. When the alarm is enabled, parameter settings B001 (Selection of Automatic
Restart Mode) and B002 (Allowable Under-voltage Power Failure Time) are not valid.

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

B001 Selection of automatic

restart mode

Select inverter restart method,
four option codes:
00... Alarm output after trip,
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.

✘ ✔

00

00

IPS POWR ALM

B002 Allowable under-

voltage power failure
time

The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.

✘ ✔

1.0

1.0

sec.

IPS Time 0001.0s

B003 Retry wait time before

motor restart

Time delay after under-voltage
condition goes away, before
the inverter runs motor again.
Range is 0.3 to 100 seconds.

✘ ✔

1.0

1.0

sec.

IPS Wait 0001.0s

B004 Instantaneous power

failure / under-voltage
trip alarm enable

Two option codes:
00... Disable
01... Enable

✘ ✔

00

00

sec.

IPS TRIP OFF

B005 Number of restarts on

power failure / under-
voltage trip events

Two option codes:
00... Restart 16 times
01... Always restart

✘ ✔

00

00

sec.

IPS RETRY 16