Network Detection Signal

The Network Detection Signal output indicates the general status of network communi-
cations. The inverter has a programmable watchdog timer to monitor network activity.
Parameter C077 sets the time-out period. If communications stop or pause longer than
the specified time-out period, the Ndc output turns ON.

Additionally, the inverter can respond to a communications time-out in various ways.
Refer to the following diagram (top of next page). You configure the desired response
via function C076, Communications Error Select. This selects whether or not you want
the inverter to trip (alarm with error code E60) and whether to stop the motor or just let it
coast. Together, parameters C076 and C077 set the network detection watchdog time-out
and the inverter’s response.

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

08

NDc

Network Detection
Signal

ON

when the communications watchdog timer
(period specified by C077) has timed out

OFF

when the communications watchdog timer is
satisfied by regular communications activity

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

C076, C077

Notes:

To disable the communications watchdog timer, set
C077=00.00 sec.

If you set Communications Error Select to
“Disable” (C076=02), you still have the option of
using the Network Detection Signal and setting the
watchdog time-out period with C077.

RY

+

Example (requires output configuration—
see page

3–54

):

Inverter output
terminal circuit

NDc

12 11

CM2

Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages

4–36

and

3–54

):

AL0

AL2

AL1

Inverter logic
circuit board

See I/O specs
on page

4–6

.

NDc

Load

Power