Analog Input Current/Voltage Select

The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input
terminals for external frequency control. When intelligent input [AT] is ON, you can set
the output frequency by applying a current input signal at [OI]-[L]. When the [AT] input
is OFF, you can apply a voltage input signal at [O]-[L] to set the output frequency. Note
that you must also set parameter A001 = 01 to enable the analog terminal set for control-
ling the inverter frequency.

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

16

AT

Analog Input
Voltage/current
Select

ON

Terminal OI is enabled for current input (uses
terminal L for power supply return)

OFF

Terminal O is enabled for voltage input (uses
terminal L for power supply return)

Valid for inputs:

C001, C002, C003, C004,
C005

Required settings:

A001 = 01

Notes:

If the [AT] option is not assigned to any intelligent
input terminal, then inverter uses the algebraic sum
of both the voltage and current inputs for the
frequency command (and A001=01).

When using either the analog current and voltage
input terminal, make sure that the [AT] function is
allocated to an intelligent input terminal.

Be sure to set the frequency source setting
A001=01 to select the analog input terminals.

Example (default input configuration shown
for –FU models; –FE models require input
configuration—see page

3–47

):

See I/O specs on page

4–6

.

AT

1

2

3

4

5

L

PCS

+ –

4-20 mA, AT=ON

0-10 V, AT=OFF

L

H O OI

AM