Using Intelligent Output Terminals

Oper

ations

and Monitor

ing

4–38

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is in
Run Mode. The output logic is active low, and
is the open collector type (switch to ground).

[FW],

[RV]

Output

freq.

Run

Signal

start freq.

t

ON

1
0

1
0

B082

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

00

RUN

Run Signal

ON

when inverter is in Run Mode

OFF

when inverter is in Stop Mode

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

(none)

Notes:

The inverter outputs the [RUN] signal whenever the
inverter output exceeds the start frequency specified
by parameter B082. The start frequency is the initial
inverter output frequency when it turns ON.

The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.

RY

+

Example for terminals [11] and [12] (default
output configuration shown—see page

3–54

):

Inverter output
terminal circuit

RUN

Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages

4–36

and

3–54

):

AL0

AL2

AL1

Inverter logic
circuit board

See I/O specs
on page

4–6

.

RUN

Load

Power

supply

12 11

CM2