Analog output operation, Analog output operation 4–55, Analog output operation” on – Hitachi L2002 User Manual

Page 199

Advertising
background image

L200

2

Inverter

Oper

ations

and Monitor

ing

4–55

Analog Output Operation

In inverter applications it is useful to monitor
the inverter operation from a remote location or
from the front panel of an inverter enclosure. In
some cases, this requires only a panel-mounted
volt meter. In other cases, a controller such as a
PLC may provide the inverter’s frequency
command, and require inverter feedback data
(such as output frequency or output current) to
confirm actual operation. The analog output
terminal [AM] serves these purposes.

The inverter provides an analog voltage output on terminal [AM] with terminal [L] as
analog GND reference. The [AM] can output inverter frequency or current output value.
Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or
reverse motor rotation. Use C028 to configure terminal [FM] as indicated below.

The [AM] signal offset and gain are adjustable, as indicated below.

The graph to the right shows the effect of the
gain setting. To calibrate the [AM] output for
your application, follow the steps below:

1. Verify that the inverter is in Stop Mode.

2. Use C086 to adjust the offset voltage. The

factory default (0V) is the correct value for
most cases. Otherwise, you can have a
positive voltage at zero speed or current.

3. Run the motor at the full scale speed.

a. If [AM] represents output frequency, use

B080 to set the voltage for full scale
output (up to 10V).

b. If [AM] represents motor current, use B080 to set the voltage for full scale

output. Remember to leave room at the upper end of the range for increased
current when the motor is under heavier loads.

Func.

Code

Description

Range

C028

00

Output frequency

0 – Max. frequency (Hz)

01

Output current

0 – 200%

Func.

Description

Range

Default

B080

[AM] analog signal gain

0 to 255

100

C086

[AM] terminal offset tuning

0 – 10V

0.0

A GND

Analog

Voltage

Output

See I/O specs on page

4–6

.

+

10VDC

full scale,

1mA max

L

H O OI

AM

[AM]

Hz

or

A

0

1/2 full

scale

Full

scale

output

B080=200%

B080=100%

B080=50%

10V

5V