L200

2

Inverter

Appendix B

B–21

ModBus Holding Registers

The following tables list the holding registers for the inverter interface to the network.
The table legend is given below.

Function Code - The inverter’s reference code for the parameter or function (same as

inverter keypad display)

Name - The standard functional name of the parameter or function for the inverter

R/W - The read-only or read-write access permitted to the data in the inverter

Description - How the parameter or setting works (same as Chapter 3 description).

Register - The network register address offset for the value, in hex and decimal.

Actual network address is 40001 + offset. Some values have a high-byte and low-byte
address.

Range - The numerical range for the network value that is sent and/or received

TIP: The network values are binary integers. Since these values cannot have an
embedded decimal point, for many parameters it represents the actual value (in engineer-
ing units) multiplied by a factor of 10 or 100. Network communications must use the
listed range for network data. The inverter automatically divides received values by the
appropriate factor in order to establish the decimal point for internal use. Likewise, the
network host computer must apply the same factor when it needs to work in engineering
units. However, when sending data to the inverter, the network host computer must scale
values to the integer range listed for network communications.

• Resolution - This is the quantity represented by the LSB of the network value, in

engineering units. When the network data range is greater than the inverter’s internal
data range, this 1-bit resolution will be fractional.

List of Holding Registers

Func.

Code

Name

R/W

Description

Network Data

Reg.ister

Range

Res.

hex

dec.

Output frequency
command

Inverter output frequency (set
A001=03 to enable this
network register),
range is 0.0 to 400.0 Hz

0002h

00002

0 to

4000

0.1 Hz

Inverter status

R/W 00 ...Initial status

01 ...(Reserved)
02 ...Stop Mode
03 ...Run Mode
04 ...Free-run stop (FRS)
05 ...Jogging
06 ...DC braking
07 ...Retry
08 ...Trip alarm
09 ...Under-voltage

0003h

00003

0 to 9