Setting up at the system level – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 128

Advertising
background image

Publication 1394-5.0 — May 2000

7-4

Commissioning Your 1394 Analog Servo System

7.

Setting Up at the System Level

This procedure assumes that you have wired your 1394 Analog Servo
System and have completed the procedure Removing and
Re-Applying Power
earlier in this chapter.

When the LEDs on the system and axis modules are all flashing green
and the Sys Ready message appears on the HIM, you are ready to
begin these procedures.

To perform system-level setup:

1. At the HIM, press ENTER. A message similar to the following

appears:

2. Press either the up or down arrow key until the following appears:

3. Press ENTER. The following message appears:

4. Press ENTER. A message similar to the following appears:

5. Press SEL. The cursor moves to the bottom line.

6.

If the system module LED:

Then:

Flashes green and the following
appears on the HIM:

Sys Ready

The control and bus power are
active, but the modules are not
enabled. Go to Setting Up at
the System Level
.

Flashes red and green, flashes
red, remains solid red, does not
illuminate

You may have a wiring
problem. Go to the
Troubleshooting chapter.

Choose Mode
Display

Choose Mode
Start Up

ALLEN-BRADLEY
COPYRIGHT 1994

Line Voltage
460 Volts AC

If you are using:

Do this:

480 V AC

Press ENTER. The system records your
choice.

360 V AC

1. Press either the up or down arrow key

until 360 Volts AC appears.

2. Press ENTER. The system records

your choice.