Determining your type of input power, Grounded power configuration – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 52

Advertising
background image

Publication 1394-5.0 — May 2000

3-6

Wiring System, Axis, and Shunt Modules, and Motors (for all systems)

Determining Your Type of Input
Power

Before you ground or wire your 1394 system you must determine the
type of 360/480V input power you will be connecting to. The 1394
system is designed to operate in both grounded and ungrounded
environments.

Grounded Power Configuration

As shown in the figure below, the grounded power configuration
allows you to ground your 3-phase power at a neutral point. Each
1394 system module has a factory-installed jumper configured for
grounded power distribution. If you determine that you have
grounded power distribution in your plant you do not need to modify
your system.

Figure 3.2
Grounded Power Configuration

Status

U

V

W

Conduit/4-Wire Cable

Ground grid or

Power distribution ground

PE

PE1

PE3 (drain/shield)

PE2 (wire 8)

W1 (wire 3)

V1 (wire 2)

U1 (wire 1)

1326 motor
power cable

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.