Mounting your 1394-dclm – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 41

Advertising
background image

Publication 1394-5.0 — May 2000

Installing Your 1394 (applies to all systems)

2-11

Mounting Your 1394-DCLM

Two 1394 system power buses can be linked by connecting two
DCLMs together. This procedure is application specific and requires
proper implementation. Please contact your Allen-Bradley sales
representative for more information.

When using the 1394-DCLM for energy storage, the power plug must
be installed (refer to Figure 2.10 for location).

Figure 2.10
Locating the Power Plug

Mounting the External Shunt
Resistor for 5 and 10 kW System
Modules

If your 5 or 10 kW 1394 system module requires a means of
dissipating regenerative energy that exceeds the capacity of the
internal shunt resistor, install a 1394 External Shunt Resistor Kit
(catalog number 1394-SR10A).

To install the 1394-SR10A Shunt Resistor Kit use two M10 (3/8 in.)
bolts and mount the external shunt resistor assembly vertically on a
flat rigid metal surface that will not be subjected to shock, vibration,
moisture, oil mist, dust or corrosive vapors.

Note: To extend the leadwire length up to 15 m (49 ft total overall

length), use MTW, 105

°

C, (302

°

F) Class H insulated wire (UL

styles 3349, 3374, or equivalent).

Mounting External Shunt Modules
for 22 kW System Modules

If you are using a 22 kW system module, you must use a shunt
module (1394-SR9A, -SR9AF, -SR36A or -SR36AF). An external
shunt module is required for 22 kW system modules because there is
no internal shunt resistor.

DC Link
Module

1394 Digital Servo Controller

System Module

Allen-Bradley

DC Link Module

Power Plug

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.

!

ATTENTION: To avoid the hazard of shock or burn
and ignition of flammable material, appropriate
guarding must be provided. These resistors can reach
temperatures in excess of 350

°

C (662

°

F). Install per

local codes.

Advertising
This manual is related to the following products: