Publication 1394-5.0 — May 2000

9-24

Troubleshooting

4. Check the circuit resistance of the two DCLM fuses by

connecting the probes of an ohm meter as described in the table
below. Refer to Figure 9.5 for the connector locations.

Figure 9.5
Checking for a Blown Fuse

Connect the
red lead to:

Connect the
black lead to:

If the meter
reading is:

The 1394-DCLM fuse is:

Top bus (DC+)
power connector

Left front
socket

Open (high ohms)

Blown. Replace the
1394-DCLM.

Short (low ohms)

Good.

Bottom bus (DC-)
power connector

Right front
socket

Open (high ohms)

Blown. Replace the
1394-DCLM.

Short (low ohms)

Good.

Slide mechanism

Top bus (DC+)
power connector

Bottom bus (DC-)
power connector

Left front

socket

Right front
socket

1394-DCLM