Publication 1394-5.0 — May 2000

Specifications

A-5

User-Supplied Contactor (M1)

The table below shows the requirements for the contactor that you
must supply.

User-Supplied Line Input Fusing

The table below shows the requirements for the input fusing that you
must supply.

User-Supplied 24V Logic Input Power

The table below shows the requirements for the 24V logic input
power that you must supply.

The contactor:

For the 1394-SJT05 and
-SJT10 (Series A and B) is:

For the 1394C-SJT05 and
-SJT10 (Series C) is:

For the 1394

x-SJT22 is:

Rating

600V AC, 43A

1

600V AC, 23A

600V AC, 37A

Recommended

types:

AC Coil Operation

Allen-Bradley 100-C43

x10

2,3

Allen-Bradley

100-C23

x10

2,3

Allen-Bradley

100-C37

x10

2,3

DC Coil Operation

Allen-Bradley 100-C43Z

x10

2

Allen-Bradley

100-C23Z

x10

2

Allen-Bradley

100-C37Z

x10

2

1

Consider using a 60A contactor when the total capacitance of the axis modules is greater than 880 µF.

2

x indicates coil voltage.

3

A surge suppressor is required.

The Recommended type of fuse for:

Is:

Rating

1394-SJT05 systems

Series A and B

Bussmann FRS-R-20A or
equivalent

600V AC, 20A

1394C-SJT05 systems

Series C

Bussmann KTK-R-20 or
equivalent

600V AC, 20A

Bussmann LPJ-SP 20 or
equivalent

600V AC, 20A

1394-SJT10 systems

Series A and B

Bussmann FRS-R-30A or
equivalent

600V AC, 30A

1394C-SJT10 systems

Series C

Bussmann KTK-R-30 or
equivalent

600V AC, 30A

Bussmann LPJ-SP 30 or
equivalent

600V AC, 30A

1394

x-SJT22 systems

Bussmann FRS-R-35 or
equivalent

600V AC, 35A

Bussmann LPS-RK-SP 40
or equivalent

600V AC, 40A

Bussmann LPJ-SP 45 or
equivalent

600V AC, 45A

24V logic input
voltage

Frequency

Current

1

Recommended Fuse

If you have:

The current draw for user-
supplied power supply
must not exceed:

19-28V AC RMS,
single phase or

50/60 Hz

1 axis

3.5A

Bussmann MDA-15
or equivalent

2 axis

4.4A

18.75-31.25V DC

3 axis

5.2A

4 axis

6.0A

1

The power supply should be rated for 15A or greater inrush current upon power up.