Specifications

A-9

Refer to the following table for fuse replacement information.

Environmental Specifications

Mount the 1394 in an enclosure that is clean and dry [IP55 protection
rating minimum (IEC publication 529)]. For enclosures ventilated
with ambient air, be sure to have appropriate filtering to protect
against contamination. Keep the ambient air temperature between 0°
and 50° C (32° and 122° F) and the humidity between 5% and 95%,
non-condensing.

The 1394 can operate at elevations to 1000 meters (3300 ft) without
derating, however, the continuous current rating must be derated by
3% for each additional 300 m (1000 ft) up to 3000 m (10,000 ft).
Consult with your local Allen-Bradley Sales Representative prior to
operating at over 3000 m (10,000 ft).

Refer to the table below for 1394 shock and vibration specifications.

If your 1394-SR9A, -SR9AF,
-SR36A, and -SR36AF shunt
module:

You need a:

Has the UL mark

Bussmann 600V DC 50A fuse (FWP50A14F) or
equivalent.

Does not have the UL mark

Bussmann 600V DC 40A fuse (170N2013) or
equivalent.

Mode

Maximum Shock

Maximum Vibration

Operating

15g

1g

Non-operating

30g

2.5g