Publication 1394-5.0 — May 2000

4-6

Wiring 1394 GMC and GMC Turbo Systems

Wire:

Description:

Terminal connections for
1394

x-SJTxx-C, -C-RL

and -T, -T-RL systems:

Terminal connections for
1394C-SJT

xx-L and

-L-RL systems:

Mandatory
or Optional:

REG 5V, 24V,
COM

High-speed, optically-isolated filtered
registration input for each axis. Inputs can
be either 5 or 24V DC. Refer to Figure 4.5 for
typical registration device inputs.

Note: To further reduce electrical noise, a
dedicated power supply may be required for
the registration sensors.

You can disable the registration input filters
by removing jumpers P0-P3 on the input
wiring board.

For 5V
TB1 16 (axis 0)
TB2 16 (axis 1)
TB1 20 (axis 2)
TB2 20 (axis 3)

For 24V
TB1 17 - 18 (axis 0)
TB2 17 - 18 (axis 1)
TB1 21 - 22 (axis 2)
TB2 21 - 22 (axis 3)

For COM
(used with 5V and 24V)
TB1-18 (axis 0)
TB2-18 (axis 1)
TB1-22 (axis 2)
TB2-22 (axis 3)

For 5V
TB1 16 (axis 0)
TB2 16 (axis 1)

For 24V
TB1 17 - 18 (axis 0)
TB2 17 - 18 (axis 1)

For COM
(used with 5V and 24V)
TB1-18 (axis 0)
TB2-18 (axis 1)

Optional

A TEST 1
A TEST 2
A TEST COM

Two software-programmable outputs are
available:

A voltage corresponding to the motor
velocity and direction of rotation will be
present between these terminals.

±

1.0V/

krpm is available. Minimum impedance that
can be placed across this output is 10k ohm.

A voltage corresponding to positive and
negative current will be present between
these terminals.

±

2.5V DC equals 100% of

motor continuous current rating.

±

5.0V DC

equals 200%. Minimum impedance that can
be placed across this output is 10k ohms.

Any axis analog current/voltage output may
be linked to either analog output using
internal software parameters. By default
Axis 0 velocity is linked to A TEST 0 and
Axis 0 current is linked to A TEST 1.

TB1-24 (A TEST 0)
TB1-25 (A TEST 1)
TB1-26 (A TEST COM)

TB1-24 (A TEST 0)
TB1-25 (A TEST 1)
TB1-26 (A TEST COM)

Optional

DRIVE OK 1/2

When you apply 24V AC/DC control power
to the system and no system faults are
detected, the Drive OK relay contact closes.
The contact remains closed until a drive fault
occurs, the DC bus voltage is lost, or you
remove 360/480V input power from the
system module. If a drive fault is detected or
the DC bus voltage is lost, the relay contact
opens. You can wire the Drive OK contacts
into the Estop string to open the main power
contactor if a fault occurs. The contact rating
is 115V AC or 24V DC, 1A.

TB2 terminals 24 and 25

TB2 terminals 24 and 25

Mandatory

Advertising