100% torq vel, 300%torq vel, Anlg vel ofst – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 140: Anlg vel scal, Atune current

Advertising
background image

Publication 1394-5.0 — May 2000

8-4

Configuring Your 1394 Analog Servo System

[100% Torq Vel]

Motor velocity at 100% rated motor torque.

Note: Before making modifications to Mtr Data
parameters, [Motor Type] must be set to "custom
motor".

Parameter Numbers

392

Parameter Group

Mtr Data

Display Units

rpm

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value

1 rpm

Maximum Value

8000 rpm

Default Value

This is determined by the motor catalog number.

[300%Torq Vel]

Motor velocity at 300% rated motor torque.

Note: Before making modifications to Mtr Data
parameters, [Motor Type] must be set to "custom
motor".

Parameter Numbers

388

Parameter Group

Mtr Data

Display Units

rpm

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value

1 rpm

Maximum Value

8000 rpm

Default Value

This is determined by the motor catalog number.

[Anlg Vel Ofst]

An offset value that can be used on an analog
velocity input to counter voltage offsets on that
input. This value is added after the input scaling
has taken place, therefore changing the analog
input scaling will change this offset
compensation.

Parameter Numbers

276, 277, 278, 279

Parameter Group

Vel Cmd Data

Display Units

rpm

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value-

496.00 rpm

Maximum Value+

496.00 rpm

Default Value

0.00 rpm

[Anlg Vel Scal]

Use this parameter to determine how the A/D
converter value is scaled. It is set to the number
of motor rpm that is to represent 1 volt of input
command. The desired input velocity command
voltage to motor rpm scaling is accomplished
with this parameter. The default setting is 500
rpm/volt. Use the following formula if the
maximum motor speed (rpm) and maximum
velocity command (volts) are known.

Parameter Numbers

272, 273, 274, 275

Parameter Group

Vel Cmd Data

Display Units

rpm/v

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value-

1000.0 rpm/v

Maximum Value

+1000.0rpm/v

Default Value

+500.0 rpm/v

for example:

[ATune Current]

The motor current used while an auto tune cycle
is executing is specified with this parameter. In
most cases, the default setting will be
satisfactory.

Parameter Numbers

288, 289, 290, 291

Parameter Group

ATune Config

Display Units

amps

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value

10% rated motor current

Maximum Value

200% rated motor current

Default Value

50% rated motor current

3000RPMMaximum

8VDCMaximumCommand

-----------------------------------------------------------------------------

3000RPM

Volts

----------------------------

=

MaximumDesiredMotorRPM
Max

i

mumVelocityCommand

------------------------------------------------------------------------------------

RPM

Volts

---------------

=