DH-485 Specifications

The table below lists the DH-485 specifications for the system
module (1394x-SJTxx-C-xx, -L-xx, and -T-xx systems).

Flex I/O Specifications

The table below lists the Flex I/O specifications for the system
module (1394x-SJTxx-C-xx, -L-xx, and -T-xx systems).

The:

Is:

Number of DH-485 channels

One; replaces serial port B when used

Channel type

Optically isolated half-duplex RS-485

Baud rate

9,600 or 19.2 kbaud (user-selectable)

Front panel connectors

Two RJ-45 jacks (+24 V is not provided)

RS-485

User-selectable 220 ohms resistor via internal switch

Node address

User-selectable between 0 and 31 inclusive

Node type

Token-passing master

Accessible data type

• One binary file (B3) for up to 16,384 bits
• One integer file (N7) for up to 1,024 16-bit values
• One floating point file (F8) for up to 512 32-bit values
• One ASCII string file (A) for up to 2,048 characters
• Nine user-configured files; each can be individually

configured as any of the above types or as a BCD file for
floating point simulation

The:

Is:

Maximum number of Flex I/O
modules

8

Compatible modules

• 1794-IB16; 16 24V DC discrete inputs
• 1794-IA8; 8 115V AC discrete inputs
• 1794-IE8; 8 current/voltage analog inputs
• 1794-OB16; 16 24V DC discrete outputs
• 1794-OA8; 8 115V AC discrete outputs
• 1794-OE4; 4 current/voltage analog outputs
• 1794-IE4XOE2; 4 current/voltage analog inputs and 2

current/voltage analog outputs

• 1794-IB10XOB6; discrete combination module
• 1794-OW8 relay output module
• 1794-IF4I isolated analog input module
• 1794-OB16P discrete output (protected)

Interface

Direct; no 1794-ASB or other adapter required