Publication 1394-5.0 — May 2000

3-16

Wiring System, Axis, and Shunt Modules, and Motors (for all systems)

Terminal Block Locations for a 22 kW System Module

All 22 kW system module components use IEC terminals for power
connections. You will wire the system and axis modules using the
power terminal block conveniently located at the bottom front of the
system and axis modules. To gain access to the input power terminals,
open the system module door and look in the lower right corner.
Figure 3.12 details the order of the terminal blocks.

Figure 3.12
Terminal Block for 22 kW System Module

Note:

Refer to Appendices A and B for information about three-phase
input fusing and circuit breaker information as related to the
power input. Refer to the section Connecting Your Shunt
Module
for information about wiring the shunt module to the
22 kW system module.

!

ATTENTION: To avoid personal injury and/or
equipment damage, ensure installation complies with
specifications regarding wire types, conductor sizes,
branch circuit protection, and disconnect devices. The
National Electrical Code (NEC) and local codes
outline provisions for safely installing electrical
equipment.

Wire:

Description:

Maximum wire size:

Connects to
terminal(s):

Required
(Y/N):

24V Logic

A user-supplied 24V AC rms or 24V DC power source. Refer to
Appendix A for 24V input power specifications.

3.3 mm

2

(12 AWG)

W1 and W2

Y

360/480V AC power input 360/480V AC, three-phase power input. Refer to

Appendix A for

system specifications for rated AC input voltage, tolerance, and
source impedance.

8.4 mm

2

(8 AWG)

U, V, and W

Y

Input Power Neutral

Three-phase input neutral (present only on grounded power
configurations).

8.4 mm

2

(8 AWG)

System ground bar
(Series A and B)

N

PE (Series C)

N

PE Ground

The1394’s ground connection to the bonded system ground bar
on the subpanel.

8.4 mm

2

(8 AWG)

PE (Series A and B)

Y

System module ground
bar (Series C)

Y

External Shunt Module

Used to dissipate excess regenerative energy from the system
module.

8.4 mm

2

(8 AWG)

DC+ and COL

Y