Configuring Your 1394 Analog Servo System

8-19

[Rem. Data In/Out:Px]

This series of parameters represent linkable
inputs and outputs to the SCANport "analog"
inputs and outputs for each of the six available
ports.

Parameter Numbers

58-69

Parameter Group

Linear List

Display Units

None

Parameter Type

Read Only

Linkable

In=No, Out=Yes

[Resolvr Posn]

This parameter supplies the position feedback
count. 65,535 represents the counts per 1/2
revolution.

Parameter Numbers

216, 217, 218, 219

Parameter Group

Monitor Parms

Display Units

None

Parameter Type

Read Only

Linkable

No

[Resolvr Turns]

The number of resolver electrical turns is
supplied by this parameter. When these values
reach maximum, the value drops to -32768 and
begins to again count up and down.

Parameter Numbers

244, 245, 246, 247

Parameter Group

Monitor Parms

Display Units

None

Parameter Type

Read Only

Linkable

No

[Rg Power Usage]

Displays the present average power regenerated
by all motors back to the system module.

Active on all Smart Power 22 kW systems and 5
and 10 kW (Series C or later) systems.

Parameter Numbers

40

Parameter Group

Smart Sys Data

Display Units

%

Parameter Type

Read Only

Linkable

No

[Shunt Kl]

Shunt resistor long time constant, measured in
seconds.

Active on all Smart Power 22 kW systems and 5
and 10 kW (Series C or later) systems.

This parameter only needs to be configured
when you are using custom resistors.

Note: [Shunt Type] must be set to "custom shunt"
before making modifications to this shunt
parameter (44-48).

Parameter Numbers

47

Parameter Group

Linear List

Display Units

S

Parameter Type

Read/Write

Change While Running

No

Minimum Value

1

Maximum Value

255

Default Value (22 kW)

70

Default Value (5 and 10 kW)

10

[Shunt Ks]

Shunt resistor short time constant, measured in
seconds.

Active on all Smart Power 22 kW systems and 5
and 10 kW (Series C or later) systems.

This parameter only needs to be configured
when you are using custom resistors.

Note: [Shunt Type] must be set to "custom shunt"
before making modifications to this shunt
parameter (44-48).

Parameter Numbers

46

Parameter Group

Linear List

Display Units

ms

Parameter Type

Read/Write

Change While Running

No

Minimum Value

250

Maximum Value

2550

Default Value (22 kW)

250

Default Value (5 and 10 kW)

250