Publication 1394-5.0 — May 2000

B-18

Interconnect and CE Diagrams

The example below shows 1394 (Series A and B) axis modules wired
for thermal fault monitoring. Depending on how the 1394 GMC
system is configured, the fault can be used to disable one or all of the
four axis modules. Two separate 24V DC power supplies and four
relays (CR2-CR5) are included to isolate the THERM FLT inputs
from conducted noise.

Figure B.11
Isolated Series E-Stop with Thermal Fault Monitoring

CR3

CR2

CR5

TB2

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20

TB1

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27

21
22
23
24
25
26
27

24V DC

I/O

Power Supply

+24V DC

24V DC com

CR3

CR2

CR4

CR5

THERM FLT 1

THERM FLT 3

THERM FLT 2

THERM FLT 0

Note: 120V AC (50 or 60 Hz) power may be used in place of a 24V DC power supply for motor thermal switch circuits.

1394 GMC Input Wiring Board

1394

x-SJTxx-C

1394

x-SJTxx-C-RL

AND

1394

x-SJTxx-T

1394

x-SJTxx-T-RL

Axis 0

Axis 1

Axis 2

Axis 3

24V DC

Power Supply

+24V DC

24V DC com

Motor

Thermal

Switch

CR4

TB1

TB2

1394-AM

xx

4 3 2 1

4 3

4 3

2 1

TB1

TB2

1394-AM

xx

4 3 2 1

4 3

4 3

2 1

TB1

TB2

1394-AM

xx

4 3 2 1

4 3

4 3

2 1

TB1

TB2

1394-AM

xx

4 3 2 1

4 3

4 3

2 1