Defining limits – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 134

Advertising
background image

Publication 1394-5.0 — May 2000

7-10

Commissioning Your 1394 Analog Servo System

Defining Limits

This procedure assumes that you have wired your 1394 Analog Servo
System and have completed the procedures in the following sections
of this chapter:

Removing and Re-Applying Power

Setting Up at the System Level

Setting Up Analog Test Points

Defining Your Motors

Defining a Reference Source for Your Axes

To define limits:

1. When the Ax: Current Limit message appears, press SEL. The

cursor moves to the bottom line.

2. Press either the up or down arrow until the appropriate current

limit appears.

3. Default values are set by the motor type you selected. You cannot

exceed this value.

4. Press ENTER. The system records your choice and the cursor

moves to the top line.

5. Press ENTER. A message similar to the following appears:

Note: Default values are set by the motor type you

selected. You cannot exceed this value.

6. Press SEL. The cursor moves to the bottom line.

7. Press either the up or down arrow until the appropriate velocity

limit appears.

8. Press ENTER. The system records your choice and the cursor

moves to the top line.

9. Press ENTER. A message similar to the following appears:

10. Go to Auto Tuning.

Ax:Vel Lim

5000.0 rpm

Ax:ATune Select

Idle