Connecting thermal and brake leads to axis modules, Required tools and equipment – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 66

Advertising
background image

Publication 1394-5.0 — May 2000

3-20

Wiring System, Axis, and Shunt Modules, and Motors (for all systems)

Connecting Thermal and Brake Leads to Axis Modules

Axis modules provide terminating points for the motor power,
thermal sensor, and brake. Axis module wiring is identical for all
available axis module ratings.

Figure 3.13
Locating TB1 and TB2

Important: Noise filters on the motor thermal sensor and brake

connectors (TB1 and TB2) add capacitance (1.0

µF)

from each leg of the thermal switch and motor
brake leads to ground. This should be considered
when selecting

ground fault circuits.

Connect the motor thermal sensor and brake lead to the Axis Module
at TB1 and TB2. Each axis module comes with a brake and thermal
connector kit. Refer to Appendix D for more information.

Required Tools and Equipment

A small, flathead screwdriver

One 1326-CPx1-xxx motor power cable for each axis

One axis module connector kit (catalog number 1394-199) for
thermal switch and brake inputs. You will need one kit per axis
module as each kit contains two connectors.

TB

1

TB

2

1

4

1

4

U1

V1

W1

PE1

PE2

PE3

Terminal:

Description:

TB1-1, 2

Thermal Sensor Input from Motor Cable

TB1-3, 4

Brake 24V DC from Motor Cable

TB2-1, 2

Brake 24V DC from Fault System

TB2-3, 4

Thermal Sensor Output to Fault System