Install filter and NTND26 cable (for MSDL and DCHIP cards in different Large System equipment

rows)

203

5

Use the NTMF04BA Extension Cable to connect the DCH (P5)
connector of the NTCW84KA to the inward side of the 15-pin I/O
panel filter connector.

—End—

Small System cable installation

Follow the steps in

Procedure 13 "Installing cables on Small Systems" (page

203)

for Small System cable installation.

Procedure 13

Installing cables on Small Systems

Step

Action

1

Set the switches and jumper plugs in the NTAK02 SDI/DCH card as
shown. See

Table 45 "NTAK02 SDI/DCH switch settings for IP Trunk

3.01 (and later) DCHIP" (page 203)

and

Table 46 "NTAK02 SDI/DCH

jumper settings for the IP Trunk 3.01 (and later) DCHIP" (page 203)

.

Table 45
NTAK02 SDI/DCH switch settings for IP Trunk 3.01 (and later) DCHIP

Port 1

SW 1-1

SW 1-2

DCH

OFF

OFF

Port 3

SW 1-3

SW 1-4

DCH

OFF

OFF

Table 46
NTAK02 SDI/DCH jumper settings for the IP Trunk 3.01 (and later)
DCHIP

Port

Jumper

location

Strap for

DTE

Jumper

location

RS422

J7

C – B

J9

C – B

Port 1

J6

C – B

J8

C – B

J4

C – B

J2

C – B

Port 3

J3

C – B

J1

C – B

2

Connect the NTAK19FB Quad Serial I/O SDI/DCH Cable (or
equivalent) to the I/O connector for the card slot in which the
SDI/DCH card is installed.

3

If the DCHIP card is installed in the main cabinet with the SDI/DCH
card, then use NTWE04AD SDI/DCH Extension Cable (1 ft) from the

Nortel Communication Server 1000

IP Trunk Fundamentals

NN43001-563

01.01

Standard

Release 5.0

30 May 2007