X.time limiting the control speed – Burkert Type 8693 User Manual

Page 107

Advertising
background image

107

Start-up and operation of the

position controller Type 8692

22.3.8. X.TIME

limiting the control speed

Use this auxiliary function to specify the opening and closing times for the entire stroke and limit the control speeds.

When the

X.TUNE function is running, the minimum opening and closing time for the entire stroke is auto-

matically entered for

Open and Close. Therefore, movement can be at maximum speed.

Factory setting: values determined at the factory by the

X.TUNE

If the control speed is limited, values can be input for

Open and Close which are between the minimum values

determined by the

X.TUNE and 60 s.

X.TIME

Open 1

Close 1

EXIT

ENTER

INPUT

+

-

Open 1

OK

INPUT

+

-

Close 1

OK

27)

27)

Opening time for entire
stroke (in seconds)

Adjustment range:
1 – 60 seconds

Closing time for entire
stroke (in seconds)

Adjustment range:
1 – 60 seconds

Figure 60:

Operating structure X.TIME

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

Effect.of.limiting.the.opening.speed.when.there.is.a.jump.in.the.set-point.value

Set-point value

Actual value

Open

t

Valve stroke [%]
(

POS, CMD)

Figure 61:

Graph X.TIME

27)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.