Burkert Type 8693 User Manual

Page 205

Advertising
background image

205

DeviceNet

name

Description.of.the.input.data.attributes

Attribute.Address.
Class,.Instance,.
Attribute;..
Data.type,.Length

POS

Actual position

Actual value of position controller as ‰. Value range 0–1000.
However, values <0 or >1000 also possible if e.g. Autotune has
not run through correctly.

111, 1, 59;

INT, 2 byte

CMD

Nominal position

Set-point value of position controller as ‰. Value range 0–1000.

111, 1, 58;

UINT, 2 byte

PV

78)

Process actual value (process value)

Actual value of process controller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL), max. value range –999–9999,

depending on internal scaling.

120, 1, 3;

INT, 2 byte

SP

78)

Process set-point value

Set-point value of process controller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL), max. value range –999–9999,

depending on internal scaling.

120, 1, 2;

INT, 2 byte

ERR

Error

Indicates the number of the process value (output) which was not
written. The value is retained until it is deleted with “1” by acycli-
cally writing the “Error” attribute (access via Explicit Message –
Set Attribute Single).

HEX

0X14 INP

0X15 SP

100, 1, 1;

USINT, 1 byte

Table 54:

78)

relevant only for type 8693 and when process controller activated.

english