114

Start-up and operation of the
position controller Type 8692

22.3.13. BINARY-IN

activation of the binary input

This function activates the binary input.

The following settings can be implemented for this:

• Approaching the safety position

or

• Switching over the MANUAL/AUTOMATIC operating mode

SELEC

SafePos

EXIT

BIN.IN type

Safety position

Selection
Type of the binary input

BINARY-IN

ENTER

MANU/AUTO

ENTER

Operating mode
switchover

SELEC

normally open

normally closed
(0 – 5 V = 1; 10 – 30 V = 0)

normally closed

normally open
(0 – 5 V = 0; 10 – 30 V = 1)

EXIT

Figure 67:

Operaring structure BINARY-IN

Safety.position.SAFEPOS
Approach of a safety position.

• Active

SAFEPOS menu option

The actuator moves to the lower

SAFEPOS set position.

• Inactive

SAFEPOS menu option

The actuator moves to the end position which it would specify in the isolated state.

Operating.mode.switchover.MAnu/AuTO

Switch over the operating state to MANUAL or AUTOMATIC.

• Binary input = 0

AUTOMATIC operating mode

• Binary input = 1

MANUAL operating mode

If operating mode switchover is selected, you can no longer switch over the operating mode via the
selection key on the right (MANU/AUTO).

english

Type 8692, 8693