Pv input pt 100) – Burkert Type 8693 User Manual

Page 141

Advertising
background image

141

Start-up and operation of the

position controller Type 8693

-3-

PV-SCALE - 3 - Scaling of the process controller for selection of the Pt 100

input (PV INPUT PT 100)

The

PV-SCALE function specifies the following settings for the Pt 100 signal type:

• The unit of the process actual value.

• Position of the decimal point.

• The values for the lower and upper process actual value.

If the settings for the unit of the process actual value or the position of the decimal point are input or
changed, this setting applies to all scaling values (

PVmin, PVmax, SPmin, SPmax).

+

PVmin 0

PVmin 0 *C

INPUT

OK

44)

PV SCALE

ENTER

EXIT

+

PVmax 100.0

PVmax 100.0 *C

INPUT

OK

44)

Figure 88:

Operating structure P-CONTROL-PV-SCALE - Pt100

PVmin X *X

lower scaling value for the process actual value

1. select the unit for the temperature

The unit on the display has a dark background. Press the up arrow key (+) to select from the following
units:
°C or °F.

2. input the position of the decimal point

Press the down arrow key (←) to highlight the decimal point with a dark background. Press the up arrow
key (+) to specify the position.

Adjustment range: 1 or 2

3. input the lower scaling value for the process actual value

Press the down arrow key (←) to highlight the individual positions with a dark background. Press the up
arrow key (+) to set the value.

Adjustment range: -200 ... 800

Measurement range of the Pt 100: -20 °C – 220 °C or -4 °F – 428°F

This setting specifies the reference range for the dead band of the process controller as well as for the
analogue feedback of the process actual value (option).

44)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

english

Type 8692, 8693