Bus.status.display, Bus status display – Burkert Type 8693 User Manual

Page 207

Advertising
background image

207

DeviceNet

45.

Bus sTaTus display

The bus status is indicated on the display on the device.

Display

Device.status

Explanation/Troubleshooting

BUS offline

is displayed
approx. every
3 seconds

offline

Device is not connected to the bus, the network access pro-
cedure (duplicate MAC-ID test, duration approx. 2 s) has still
not ended or device is only active network node

• Baudrate correctly set across network?

• Bus connection including plug assignment correct?

• Power supply and bus connection of the other nodes

correct?

BUS no
connection

is displayed
approx. every
3 seconds

online,

no connection to the master

Device is connected correctly to the bus, the network access
procedure has ended without errors, however there is no
established connection to the master.

BUS no
timeout

is displayed
approx. every
3 seconds

I/O connection timeout

An I/O connection is in the

TIME OUT state.

New connection establishment by master; ensure that I/O
data is transferred cyclically or, if

COS confirmed, that cor-

responding Acknowledge messages are sent by the master.

BUS critical
err

is displayed
approx. every
3 seconds

Critical bus error

Other device with the same address in the network or

BUS

OFF due to communication problems.

Change address of the device and restart device

Error analysis in the network with a bus monitor.

Table 57:

Bus status display

english

Type 8692, 8693

Advertising