Technical.data, Technical data – Burkert Type 8693 User Manual

Page 194

Advertising
background image

194

DeviceNet

38.

Technical daTa

eds file

BUER8692.EDS

icons

BUER8692.ICO

Baudrate

125 kbit/s, 250 kbit/s, 500 kbit/s (can be adjusted by pressing operator keys on the device
or via network);
Factory setting 125 kbit/s

address

0 – 63; (can be adjusted by pressing operator keys on the device or via network);
Factory setting 63

process data

7 static input assemblies
(Input: from the positioner to the DeviceNet master/scanner)
4 static output assemblies

total line length

according to DeviceNet Specification

(Total line length = total of all trunk and drop lines)

Baudrate

maximum total line length

thick cable

thin cable

125 kbaud

500 m

100 m for all baudrates

250 kbaud

250 m

500 kbaud

100 m

Table 48:

Total line length

drop line length

Baudrate

length of the drop lines

maximum length

maximum total length

drop lines in the network

125 kbaud

6 m for all baudrates

156 m

250 kbaud

78 m

500 kbaud

39 m

Table 49:

Drop line length

english

Type 8692, 8693

Advertising