. other.malfunctions, Other malfunctions – Burkert Type 8693 User Manual

Page 221

Advertising
background image

221

Maintenance and troubleshooting

On.PrOFIBuS-DP:

Display

Device.status

Explanation

Troubleshooting

BUS offline

is displayed approx. every
3 seconds

offline

Device is not connected to the
bus

• Bus connection including

plug assignment correct.

• Check power supply and

bus connection of the other
nodes.

Table 66:

Error messages PROFIBUS-DP; Type 8693

50.2. Other malfunctions

Problem

Possible.causes

remedial.action

POS = 0 (when CMD > 0 %) or
POS = 100 %, (when CMD < 100 %)
PV = 0 (when SP > 0) or
PV = PV (when SP > SP )

Sealing function (

CUTOFF) has

been unintentionally activated

Deactivate sealing function

Applies only to devices with binary
output:
Binary output does not switch

Binary output:

Current > 100 mA

Short-circuit

Check binary output connection.

Applies only to devices with process
controller:
Device is not operating as a con-
troller, despite correctly implemented
settings.

P.CONTROL menu option is in
the main menu. The device is
therefore operating as a process
controller and expects a process
actual value at the corresponding
input.

Remove

P.CONTROL menu option

from the main menu.

Table 67:

Other malfunctions Type 8693

english

Type 8692, 8693