Start-up and operation of the
position controller Type 8693

OUT DEV.X alarm output for excessively large control deviation of the position controller:

→

Press the arrow keys to mark the

OUT DEV.X menu option and confirm with the selection key on the right

(SELEC).

→

Press the arrow keys to input

the limit value for the permitted control deviation in the Lim. DEV.X 1.0% menu

option and accept with the selection key on the right (OK).

The permitted control deviation

Lim. DEV.X XX must not be less than the dead band.

→

In the

OUT BIN type menu option input the required switching status (normally open / normally closed, see

“Table 41: “).

OUT POS output of the current position with respect to a specified limit position:

→

Press the arrow keys to mark the

OUT POS menu option and confirm with the selection key on the right

(SELEC).

→

Press the arrow keys to input the

the value of the limit position in the Lim. POS 0% menu option and accept

with the selection key on the right (OK).

→

In the

OUT BIN type menu option input the required switching status (normally open / normally closed, see

“Table 41: “).

OUT BIN1

normally open

normally closed

POS > LIM

0 V

24 V

POS < LIM

24 V

0 V

Table 40:

OUT Safepos output of message: actuator in safety position:

→

Press the arrow keys to mark the

OUT Safepos menu option and confirm with the selection key on the right

(SELEC).

→

In the

OUT BIN type menu option input the required switching status (normally open / normally closed).

OUT ERR SP/CMD

55)

output sensor break:

→

Press the arrow keys to mark the

OUT ERR SP/CMD menu option and confirm with the selection key on the

right
(SELEC).

→

In the

OUT BIN type menu option input the required switching status (normally open / normally closed).

OUT ERR PV

55)

output sensor break:

→

Press the arrow keys to mark the

OUT ERR PV menu option and confirm with the selection key on the right

(SELEC).

→

In the

OUT BIN type menu option input the required switching status (normally open / normally closed).

55)

Only possible if signal level fault detection activated (see chapter entitled “25.4. SIG-ERROR Configuration of
signal level fault detection”)

english

Type 8692, 8693