Start-up and operation of the
position controller Type 8693

25.6. CAL.USER -

calibrating the actual value display and the inputs
for the process values

The following points can be manually calibrated with this function:

• Position display (

POS) 0 – 100%

• Process set-point value display (S

P)

56)

• Process actual value display (

PV)

EXIT

calibr. POS

CAL. USER

ENTER

ENTER

OPN

CLS

POS lower 0

EXIT

POS lower 0

INPUT

OK

58)

OPN

CLS

POS upper 0

POS upper 0

INPUT

OK

58)

calibr. PV

ENTER

EXIT

copyFACT->USER

RUN

Pressfor approx. 3
seconds

Reset the settings of

CAL.

USER to factory settings

calibr. SP

56)

ENTER

SP 4mA 0

EXIT

SP 4mA 0

57)

INPUT

OK

58)

SP 20mA 0

SP 20mA 0

57)

INPUT

OK

58)

Calibration of signal type 4 – 20 mA

Calibration of circuit with Pt 100

OK

58)

Figure 105: Operating structure CAL.USER-8693

Remove the

CAL.USER auxiliary function to re-activate the factory calibration.

56)

Only if external set-point value default is set in the P.CONTROL / SETUP / SP-INPUT

57)

The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).

58)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

english