Start-up and operation of the
position controller Type 8692

22.3.9. X.CONTROL

parameterisation of the position controller

Use this function to set the parameters for the position controller (dead band and amplification factors).

X.CONTROL

DBND 1 %

KXopn 1

KXcls 1

EXIT

ENTER

INPUT

+

-

DBND 1 %

OK

INPUT

+

-

KXopn 0001

OK

INPUT

+

-

KXcls 0001

OK

28)

28)

28)

Figure 62:

Operating structure X.CONTROL

dBnd

insensitivity range (dead band) of the position controller
Input the dead band as %, relating to the scaled stroke range;

i.e.

X.LIMIT Max - X.LIMIT Min (see Auxiliary function X.LIMIT).

This function causes the controller to respond from a specific control difference only. This function
protects the solenoid valves in the positioner and the pneumatic actuator.

If the auxiliary function

X.CONTROL is in the main menu while X.TUNE (Autotune of the position controller)

is running, the dead band

DBND is determined automatically depending on the friction behaviour of the

actuator. The value determined in this way is an approximate value. You can re-adjust it manually.

28)

if the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.