Start-up and operation of the
position controller Type 8693

PVmax X *X

upper scaling value for the process actual value

The unit for the temperature and the position for the decimal point is transferred from the inputs of the
lower scaling value.

1. input the upper scaling value for the process actual value

Press the down arrow key (←) to highlight the individual positions with a dark background. Press the
up arrow key (+) to set the value.

Adjustment range: -200 ... 800

Measurement range of the Pt 100: -20 °C – 220 °C or -4 °F – 428°F

This setting specifies the reference range for the dead band of the process controller as well as for the
analogue feedback of the process actual value (option)

SP INPUT - Type of set-point value default (internal / external)

This function specifies whether the set-point value default

• internal:

is implemented by pressing the keys on the positioner or

• external:

is implemented via the unit signal input.

Factory setting:

internal

SP-INPUT

ENTER

SELEC

internal

Internal set-point value default by
pressing the keys on the positioner

EXIT

external

External set-point value
default via unit signal input

Figure 89:

Operating structure P.CONTROL - SP-INPUT