General.information, Technical.data, General information – Burkert Type 8693 User Manual

Page 174: Technical data

Advertising
background image

174

PROFIBUS-DP

26.

general infOrmaTiOn

The following sections of the general operating instructions do not apply to the positioner with PROFIBUS-DP:

• Variants of the positioner

• Initial start-up

• Electrical connection

• Specifying the standard settings

Function

INPUT

Function

SPLTRNG

Function

BINARY-IN

Function

OUTPUT

Function

CAL.USER / calibr. INP

Function

CAL.USER / calibr. SP

27.

Technical daTa

The protocol sequence complies with the standard DIN 19245 Part 3.

Gsd file

BUE2C630.GSD

Bitmap files

BUE2C630.BMP

pno-id

C630 Hex

Baudrate

max. 12 Mbaud
(is set automatically by the positioner)

sync and freeze modes

are not supported

diagnosis telegram

No device-specific diagnosis

parameter telegram

No user parameters

The process data is configured in the positioner and in the PROFIBUS master.

Maximum 10 process values (total

INPUT and OUTPUT) can be transferred.

english